Model 5700 Installation and Operation Manual
4-38 151295
4.14.6 Transmitter Activated by Dry Contacts
This section describes the connection of a UL 864 listed remote station transmitter to the 5700
FACP dry contacts. The FACP contacts must be supervised by the remote station transmitter
module using end-of-line resistors (ELRs) with a value determined by the transmitter
manufacturer. Power is also provided by the remote station transmitter manufacturer. Refer to
the remote station transmitter manufacturers manual for details.